Specially Developed For The Requirements of Tomorrow
Featuring models ranging from 10 kW to 24 kW, the Fronius Symo Advanced is the ideal inverter for commercial applications. The new Advanced versions combine the benefits of the Fronius Symo with additional features zero tilt mounting, light weight and field serviceability.
Indoor and outdoor installation, tilt from 0 - 90 degree (Fronius Shade Cover required for installation angles less than 15 degrees)
Permitted humidity 2)
0 - 100 % (non-condensing)
Dimension (width)
511 mm
Dimension (height)
724 mm
Dimension (depth)
226 mm
Weight
43,4 kg
Protection class
NEMA 4X
Night time consumption
<1 W
Inverter topology
Transformerless
Cooling
Variable speed fan
Elevation
2000 m (6562 ft) with a max. input voltage of 1000 V / 3400 m (11155 ft) with a max. input voltage of 850 V
Certificates and compliance with standards
UL 1741-2010 Second Edition (incl. UL1741 Supplement SA 2016-09 for California Rule 21 and Hawaiian Electric Code Rule 14H), UL1998 (for functions: AFCI, RCMU and isolation monitoring), IEEE 1547-2003, IEEE 1547a-2014, IEEE 1547.1-2003, ANSI/IEEE C62.41, FCC Part 15 A & B, NEC 2017 Article 690, C22. 2 No. 107.1-16, UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013
DC connection terminals
6x DC+ and 6x DC- screw terminals for copper (solid / stranded / fine stranded) or aluminum (solid / stranded)
AC connection terminals
Screw terminals 14-6 AWG
Number of MPPT
2
Max. usable input current
NA
Max. usable input current total (MPPT1 + MPPT2)
51 A
Max. array short circuit current (1.5 * Imax)
76,5 A
Operating voltage range
200-1000 V
MPP Voltage Range
450-800 V
Max. input voltage (Udc max)
1000 V
Max. output power 480 V
19995 W
Max. output power 277 V
19995 W
Max. output power 240 V
NA
Max. output power 208 V
NA
Output configuration
3~ NPE 480 V
Frequency range
50-66 Hz
Nominal operating frequency
60 Hz
Power factor range
0-1 ind,/cap,
Max continuous output current 480 V
24,0 A
Max. continuous output current 277 V
24,0 A
Max. continuous output current 240 V
NA
Max. continuous output current 208 V
NA
DC reverse polarity protection
Yes
Anti islanding
internal; in accordance with UL 1741-2010, IEEE 1547-2003 and NEC
Over temperature protection
Ouput power derating/Active cooling
AFCI
Yes
Rapid shutdown compliant
Yes
Ground fault protection with isolation monitor interrupter
Yes
DC disconnect
Yes
USB (type A socket)
Datalogging and inverter update possible via USB
2x RS422 (RJ45 socket)
Fronius Solar Net, interface protocol
Wi-Fi / Ethernet / Serial / Datalogger and webserver