Generac's Smart Power Management System is designed to optimize the performance of a standby generator. The system can consist of up to 8 individual SmartManagement Modules (SMM). Unlike other load management systems that depend on another control device, the SMM modules are actually self-aware and operateautonomously.
Frequency is the true measure of generator engine performance, and does not need to factor in increased ambient temperatures, elevation changes, or generator fueltype. The modules monitor the frequency (Hz) of the power being produced by Generac's standby generators. If frequency falls below a certain threshold of acorrectly sized system, the module will automatically shed the managed loads to allow the generator to recover.
The modules can be set to a load priority between 1-8 or be set in a lock-out only mode for loads that just simply do not need to run in an outage, therefore reducingthe necessary size of the generator for a more cost-effective solution*.
It is recommended to size the generator with appropriate excess capacity to allow starting of the largest managed loads (i.e. loads with highest starting currents). Eachmanaged load of the SACM and SMM must be assigned a unique priority setting, so no two managed loads attempt to start simultaneously. See owners manual formore information.